CVE-2013-2805
Published: Mar 26, 2019
Modified: Aug 6, 2024
Description
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the “Record Data Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
| Vendor | Product | Versions |
|---|---|---|
Rockwell Automation | RSLinx Enterprise Software | affected CPR9affected CPR9-SR1affected CPR9-SR2affected CPR9-SR3affected CPR9-SR4+3 more versions |