Description

Triangle MicroWorks SCADA Data Gateway Restore Workspace Directory Traversal Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the Restore Workspace feature. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-17227.

VendorProductVersions

Triangle MicroWorks

SCADA Data Gateway

affected
5.01.01

Weaknesses (CWE)

CVSS v3.0 Details

CVSS v3.0 Vector

CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

Attack Vector

Network

Attack Complexity

Low

Privileges Required

High

User Interaction

None

Scope

Unchanged

Confidentiality

High

Integrity

High

Availability

High