CVE Database
/

CVE-2022-2502

Back to search

CVE-2022-2502

Published: Jul 26, 2023

Modified: Mar 5, 2025

PUBLISHED

CVSS v3.1

7.5

HIGH

Description

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.

VendorProductVersions

Hitachi Energy

RTU500 series

affected
RTU500 series CMU Firmware version 13.3.1
affected
RTU500 series CMU Firmware version 13.3.2
unaffected
RTU500 series CMU Firmware version 13.3.3
unaffected
RTU500 series CMU Firmware version 13.4.1

Weaknesses (CWE)

CVSS v3.1 Details

CVSS v3.1 Vector

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Attack Vector

Network

Attack Complexity

Low

Privileges Required

None

User Interaction

None

Scope

Unchanged

Confidentiality

None

Integrity

None

Availability

High