CVE Database
/

CVE-2022-40176

Back to search

CVE-2022-40176

Published: Oct 11, 2022

Modified: Aug 3, 2024

PUBLISHED

Description

A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). There exists an Improper Neutralization of Special Elements used in an OS Command with root privileges during a restore operation due to the missing validation of the names of files included in the input package. By restoring a specifically crafted package, a remote low-privileged attacker can execute arbitrary system commands with root privileges on the device, leading to a full compromise.

VendorProductVersions

Siemens

Desigo PXM30-1

affected
All versions < V02.20.126.11-41

Siemens

Desigo PXM30.E

affected
All versions < V02.20.126.11-41

Siemens

Desigo PXM40-1

affected
All versions < V02.20.126.11-41

Siemens

Desigo PXM40.E

affected
All versions < V02.20.126.11-41

Siemens

Desigo PXM50-1

affected
All versions < V02.20.126.11-41

Siemens

Desigo PXM50.E

affected
All versions < V02.20.126.11-41

Siemens

PXG3.W100-1

affected
All versions < V02.20.126.11-37

Siemens

PXG3.W100-2

affected
All versions < V02.20.126.11-41

Siemens

PXG3.W200-1

affected
All versions < V02.20.126.11-37

Siemens

PXG3.W200-2

affected
All versions < V02.20.126.11-41