Description

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

VendorProductVersions

Siemens

SIMATIC ET 200AL IM 157-1 PN

affected
0 - < *

Siemens

SIMATIC ET 200MP IM 155-5 PN HF

affected
V4.2.0 - < *

Siemens

SIMATIC ET 200SP IM 155-6 MF HF

affected
0 - < *

Siemens

SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

affected
0 - < V1.3

Siemens

SIMATIC ET 200SP IM 155-6 PN R1

affected
0 - < V6.0.1

Siemens

SIMATIC ET 200SP IM 155-6 PN/2 HF

affected
V4.2.0 - < *

Siemens

SIMATIC ET 200SP IM 155-6 PN/3 HF

affected
0 - < V4.2.2

Siemens

SIMATIC PN/MF Coupler

affected
0 - < *

Siemens

SIMATIC PN/PN Coupler

affected
0 - < V6.0.0

Siemens

SIPLUS ET 200MP IM 155-5 PN HF

affected
V4.2.0 - < *

Siemens

SIPLUS ET 200MP IM 155-5 PN HF

affected
V4.2.0 - < *

Siemens

SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL

affected
V4.2.0 - < *

Siemens

SIPLUS ET 200SP IM 155-6 PN HF

affected
V4.2.0 - < *

Siemens

SIPLUS ET 200SP IM 155-6 PN HF

affected
V4.2.0 - < *

Siemens

SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL

affected
V4.2.0 - < *

Siemens

SIPLUS ET 200SP IM 155-6 PN HF TX RAIL

affected
V4.2.0 - < *

Siemens

SIPLUS NET PN/PN Coupler

affected
0 - < V6.0.0

Weaknesses (CWE)

CVSS v3.1 Details

CVSS v3.1 Vector

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Attack Vector

Network

Attack Complexity

Low

Privileges Required

None

User Interaction

None

Scope

Unchanged

Confidentiality

None

Integrity

None

Availability

High